產品名稱:(5k-30kW) modular programmable DC power supply產品型號:Sorensen SGA / SGI SeriesSorensen SG Series (SGA/SGI)(5k-30kW) modular programmable DC power supply with exceptional load transient response, low noise and high power densityProduct OverviewThe Sorensen SG Series (hereafter SG S
產品名稱:(5k-30kW) modular programmable DC power supply
產品型號:Sorensen SGA / SGI SeriesSorensen SG Series (SGA/SGI)
(5k-30kW) modular programmable DC power supply with exceptional load transient response, low noise and high power density
Product Overview
The Sorensen SG Series (hereafter SG Series) represents the next generation of high power programmable DC power supplies. The SG Series is designed for exceptional load transient response, low noise and the highest power density in the industry. With a full 15 kW available down to 20VDC output in a 3U package the SG leads the industry in power density. The power density is enhanced by a stylish front air intake allowing supplies to be stacked without any required clearance between units.
At the heart of the SG series is a 5 kW power module. Depending on the output voltage, one to six modules can be configured in a single chassis to deliver 5 kW to 30 kW of power. Combinations of these chassis can then be easily paralleled to achieve power levels up to 150 kW. Paralleled units operate like one single supply providing total system current. Available in two control versions, the SGA has basic analog controls, while the SGI provides intelligent control features.
SGI: Advanced Intelligent Control
(Sorensen General purpose Intelligent) The SGI combines onboard intelligent controls with the outstanding power electronics common to all SG family supplies. These controls enable sophisticated sequencing, constant power mode and save/recall of instrument settings. Looping of sequences makes the SGI ideal for repetitive testing. An impressive vacuum fluorescent graphical display in eight languages, context sensitive “soft” keys and front panel keyboard simplify programming of the SGI.
SGA: Outstanding Value - Analog Control
(Sorensen General purpose Analog) The SGA, with its industry leading performance, is available for customers requiring simple front panel analog controls or external control. With the same high performance power electronics as the SGI, the SGA provides essential features like 10- turn potentiometers for setting voltage and current, 3 ½ digit LED readout plus front panel over-voltage protection (OVP) preview/adjustment and reset.
SGI / SGA Comparison Chart | |||
Feature | SGA | SGI | |
Modular Design | • | • | |
Fast Load Transient | • | • | |
Parallelable | • | • | |
Analog & Digital Summing | Optional | • | |
Direct Front Panel V/1 Control | • | • | |
3½ Digit LED Readout | • | ||
Graphics Display | • | ||
Sequencing | • | ||
Save / Recall Setups | • | ||
System Power Readouts | • | ||
Constant Power Mode | • | ||
IEEE-488.2/RS-232C | Optional | RS-232C Std IEEE-488.2 Optional | |
LXI Class C Ethernet/ RS-232 | Optional | RS-232C Std, Ethernet Optional | |
Front Panel Dust Filter | Optional (3U unit only) | Optional (3U unit only) |
Applications | ||
Burn-In | Compliance Testing | |
Materials Research | Process Control | |
Product Validation | Automotive Electronics | |
Rackmount ATE Systems | Battery Charging | |
See the SFA product page for very high current slew rate and low stored energy applications. |
Specifications
Common | |
Remote Sense | Terminals are provided to sense output voltage at point of load. Maximum line drop 5% of rated voltage per line for 40-100V models, line drop 1V of rated voltage per line for 10-20V models, 1.5V for 30V models, 2% of rated voltage per line for models 160V and greater. (Greater line drop is allowed, but output regulation specifications no longer apply). |
Parallel Operation | Up to 5 units may be paralleled for additional current within the power supply single-unit specifications, with exception of the DC output current set accuracy. Additional paralleled SG units will add 0.3% inaccuracy per unit. To parallel more than 5 units, contact factory. |
Series Operation | Up to 2 units (see Output Float Voltage) |
Input | |
Nominal Voltage 3 phase, 3 wire + ground | 208/230 VAC (operating range 187 - 253 VAC) 380/400 VAC (operating range 342 - 440 VAC) 440/480 VAC (operating range 396 - 528 VAC) |
Frequency | 47 – 63Hz , 400Hz ( 400Hz @ 208VAC, for 6U units is optional modification and does not carry CE, UL or CSA markings ) |
Power Factor | >0.9 typical for 10V - 30V, 50V, 1000V and other models with optional “PF” modification. >0.75 typical for 208/220 VAC input (40V, 60V - 800V models, 0.9 available with modification “PF”) >0.72 typical for 380/480 VAC input (40V, 60V - 800V models, 0.9 available with modification “PF”) >0.69 typical for 440/480 VAC input (40V, 60V - 800V models, 0.9 available with modification “PF”) |
Protection | ½ cycle ride-though , typical, on all three phases, 3 cycle ride through on single phase; missing phase shutdown ( 800V model 6.4 msec on all 3 phases ) |
Programming & Read-back Specifications ( with sense wires used ) | |||||
Programming | Read-Back / Monitoring | ||||
Accuracy | Resolution | Accuracy | Resolution | ||
Front panel Display | SGA: +/- (0.5%fs + 1 digit) SGI (40-1000V) +/- 0.1% of voltage at full scale SGI (40-1000V) +/- 0.4% of current at full scale | SGA: 3.5 digits SGI: 4.0 digits | SGA: +/- (0.5%fs + 1 digit) SGI, Voltage: +/- 0.1% of full scale SGI, Current: +/- 0.4% of full scale | SGA: 3.5 digits SGI: 4.0 digits | Knob control & Display read-back |
SGI (10-30V) 0.1% of set point +0.1% of voltage rating SGI (10-30V) 0.1% of set point +0.4% of current rating | SGI (10-30V) 0.1% of actual +0.15% voltage rating | ||||
Remote Analog Interface | Voltage +/-0.25% of full scale Current (40-1000V) 0.8% of full scale , (10-30V) 1.0% of full scale | N/A | (40-1000V) +/-1.0% of full scale | N/A | 25-pin D-sub connector (0~5 V or 0~10 V) |
(10-30V) +/-0.5% of full scale | |||||
Remote Digital Interface | Voltage: +/- 0.1% of full scale, Current: +/- 0.4% of full scale | +/-0.002% of full scale | Voltage: +/- 0.1% of full scale Current: +/- 0.4% of full scale | +/-0.002% of full scale | RS-232C (Standard on SGI), Optional IEEE-488.2 and Optional LXI Compliant 10/100 base-T Ethernet (see Options) |
OVP | +/- 1% of full scale | +/-0.002% of full scale | Programming range: 5-110% Configured from front panel, remote analog or via optional digital inputs | ||
User I/O | Disconnect & Polarity-reversal relay control ( Only available with Ethernet Option ) | Digital 10-pin Molex type connector Chart Below | |||
Software | IVI & CVI drivers available under DOWNLOADS at: www.ProgrammablePower.com |
Physical | |||
3U Models (10V-30V) | 3U Models (40V-1000V) | 6U Models (60V-600V) | |
Width | 19.00 in (48.3 cm) | 19.00 in (48.3 cm) | 19.00 in (48.3 cm) |
Depth | 28.09 in (71.35 cm) | 26.4 in (67.1 cm) | 27.06 in (68.8 cm) |
Height | 5.25 in (13.3 cm) | 5.25 in (13.3 cm) | 10.5 in (26.7 cm) |
Weight | (4kW, 10V 15V) ≈<65 lbs (29 kg) | (5kW) ≈ ≤60 lbs (27 kg) | (20kW) ≈ ≤140 lbs (64 kg) |
Shipping Weight | Contact factory for more product & shipping weights |
Output | ||||
Ripple & Noise (Voltage Mode, Typical) | See Output: Voltage & Current Ranges Chart above. Ripple and noise specified at full load, nominal AC input. Noise measured with 6ft. cable, 1μf at load | |||
Ripple (Current Mode) | <+/- 0.04% of full scale rms current | |||
Output Rise Time (40-800V) | ≈< 100 ms 5-95% of full scale typical - resistive load (Contact factory for model specific slew rates) | |||
Output Rise Time (10-30V) | Rise Time, ms, MAX | Condition | ||
10 | Measured from 10% to 90% of the output voltage change - resistive load, typical | |||
Output Voltage Fall Time (10-30V) | Fall Time, MS MAX | Condition | ||
No Load 1 50 | 100% CC Load 10 | 100% CR Load 10 | Measured from 90% to 10% of the output voltage change. - resistive load, typical | |
Output Current Rise Time (10-30V) | Rise Time, ms, MAX | Condition | ||
20 | Measured from 10% to 90% of the output current change - resistive load, typical | |||
Output Current Fall Time (10-30V) | Rise Time, ms, MAX | Condition | ||
10 | Measured from 90% to 10% of the output current change - resistive load, typical | |||
Line Regulation (with sense wires used) | (±10% of nominal AC input, constant load) Voltage Mode: +/- 0.01% of full scale (40-800V) Current Mode: +/- 0.05% of full scale (40-800V) Voltage Mode and Current Mode: +/- 0.05% of full scale (10-30V) | |||
Load Regulation (with sense wires used) | (no load to full load, nominal AC input) Voltage Mode: +/- 0.02% of full scale (40-800V) Current Mode: +/- 0.1% of full scale Voltage Mode: +/- 0.05% of full scale (10-30V) | |||
Load Transient Response | Recovers within 1ms to +/-0.75% of full-scale of steadystate output for a 50% to 100% or 100% to 50% load change | |||
Efficiency | 87% typical at nominal line and max load | |||
Stability | ±0.05% of set point after 30 minute warm-up and over 8 hours at fixed line, load and temperature, typical | |||
Temperature Coefficient | 0.02%/ C of maximum output voltage rating for voltage set point, typical 0.03%/ C of maximum output current rating for current set point, typical | |||
Output Float Voltage | Negative terminal within +/- 300 V of chassis potential. (We recommend the use of optional isolated analog Interface (IAI).) Supplies in "series" should be the same output voltage/current, in not system current is limited to lower of the two supplies. |
Environmental | |
Operating Temperature | 0 to 50º C |
Storage Temperature | -25º C to 65º C |
Humidity Range | Relative humidity up to 95% non-condensing, 0º C – 50º C |
Altitude | Operating full power available up to 5,000 ft. (~1,500 m), derate 10% of full power for every 1,000 feet higher; non-operating to 40,000 ft. (~12,000 m) |
Cooling | Front and side air inlet, rear exhaust. Temperature controlled, variable speed fans. Units may be stacked without spacing. |
Regulatory | Certified to UL/CSA 61010 and IEC/EN 61010-1 by a NRTL, CE Compliant, Semi-F47 Compliant. LVD Categories: Installation Category II: Pollution Degree 2; Class II Equipment: for Indoor Use Only, back panel not user accessible (see user manual for installation instructions) EMC Directive, EN 61326:1998 |
Front Panel Dust Filter | 30 PPI (Pores Per Inch) - must ensure adequate airflow and / or derate max. temperature. 3U unit only. |
Output: Voltage and Current Ranges | |||
3U | |||
Power | 4/5 kW | 8/10 kW | 12/15 kW |
Voltage | Current | ||
10 | 400 | 800 | 1200 |
15 | 267 | 534 | 801 |
20 | 250 | 500 | 750 |
30 | 167 | 334 | 501 |
40 | 125 | 250 | 375 |
50 | 100 | 200 | 300 |
60 | 83 | 167 | 250 |
80 | 63 | 125 | 188 |
100 | 50 | 100 | 150 |
160 | 31 | 63 | 94 |
200 | 25 | 50 | 75 |
250 | 20 | 40 | 60 |
330 | 15 | 30 | 45 |
400 | 12 | 25 | 38 |
500 | 10 | 20 | 30 |
600 | 8 | 17 | 25 |
800 | 6.2 | 12.5 | 18.7 |
1000 | 5 | 10 | 15 |
Output: Voltage and Current Ranges | |||
6U | |||
Power | 16/20 kW | 20/25 kW | 24/30 kW |
Voltage | Current | ||
10 | 1600* | 2000* | 2400* |
15 | 1068* | 1335* | 1602* |
20 | 1000* | 1250* | 1500* |
30 | 668* | 835* | 1002* |
40 | 500* | 625* | 750* |
50 | 400* | 500* | 600* |
60 | 333 | 417 | 500 |
80 | 250 | 313 | 375 |
100 | 200 | 250 | 300 |
160 | 125 | 156 | 188 |
200 | 100 | 125 | 150 |
250 | 80 | 100 | 120 |
330 | 61 | 76 | 91 |
400 | 50 | 63 | 75 |
500 | 40 | 50 | 60 |
600 | 33 | 42 | 50 |
800 | 25* | 31.2* | 37.5* |
1000 | 20* | 25* | 30* |
* By way of paralleling 5kW, 10kW & 15kW supplies |
Read-back Specifications | |||
Ripple & Noise | |||
Voltage | rms (20Hz-300kHz) | p-p (20Hz - 20MHz) | |
10 | 20mV | 50mV | |
15 | 20mV | 50mV | |
20 | 20mV | 60mV | |
30 | 20mV | 60mV | |
40 | 20mV | 75mV | |
50 | 20mV | 75mV | |
60 | 20mV | 75mV | |
80 | 20mV | 100mV | |
100 | 20mV | 100mV | |
160 | 25mV | 150mV | |
200 | 25mV | 175mV | |
250 | 30mV | 200mV | |
330 | 30mV | 200mV | |
400 | 30mV | 300mV | |
500 | 50mV | 350mV | |
600 | 60mV | 350mV | |
800 | 80mV | 500mV | |
1000 | 100 mV | 650 mV | |
* By way of paralleling 5kW, 10kW & 15kW supplies |
Analog User I/O Pinouts | |||
1 | Isolated Remote ON/OFF | 14 | Isolated TTL/CMOS ON/OFF Control |
2 | Isolated Circuit Return | 15 | Remote Voltage Programming |
3 | Remote Overvoltage Set | 16 | Remote Current Programming |
4 | Voltage Return for Pins 9, 15, or 21 | 17 | Fault State |
5 | Remote ON/OFF | 18 | Shutdown Fault |
6 | Circuit Common | 19 | Output Voltage Monitor |
7 | Output Current Monitor | 20 | Voltage Return for Pins 9, 15, or 21 |
8 | Local Voltage Control Monitor | 21 | Voltage Control Resistance |
9 | Remote Voltage Programming | 22 | Current Control Resistance |
10 | Remote Current Programming | 23 | Current Return for Pins 10, 16, or 22 |
11 | Local Current Control Monitor | 24 | Circuit Common |
12 | Not Used | 25 | Current Return for Pins 10, 16, or 22 |
13 | Not Used |
Digital User I/O Pinouts ( Ethernet Option Only ) | |||
1 | Fold Back Monitor | ||
2 | Direct Shutdown | ||
3 | Fault Indication | ||
4 | Trigger Out | ||
5 | Common | ||
6 | Polarity output reversal signal | ||
7 | Isolation relays relay open signal | ||
8 | Sense relays open signal | ||
9 | Common | ||
10 | Trigger in |