產品名稱:(1000W) programmable DC power supply
產品型號:Sorensen XHR Series
Sorensen XHR Series (1000W)
Programmable DC power supply in a half rack size, ideal for applications where high power and wide adjustment of output voltage or current is required, and a compact half-rack configuration is advantageous.
Product Overview
XHR provides 1000 watts of programmable DC power in a compact half-rack package. It is available in eighteen 1 kW models. Its unique features and size make XHR ideal for OEM applications where high power and wide adjustment of output voltage or current is required, and a compact half-rack configuration is advantageous.
It is stackable with a small foot print, front panel binding post connectors and a low current requirement that allows it to be plugged into a standard 120 VAC, 15 A circuit. State-of-the-art zero voltage or "soft" switching technology virtually eliminates switching transients for high efficiency, low noise and high reliability. XHR is also power-factor-corrected for low current draw (only 11 A at 120 VAC for 1000 watts) and reduced generation of input current harmonics.
The half-rack XHR is ideal as a "companion" for another half-rack instrument in a test system equipment console, eliminating the need for a blank panel while preserving vertical rack space. With a choice of rear and/or front panel connectors, XHR offers added system flexibility.
Key Features
● 85-250 VAC universal input
● Standby mode
● Constant voltage or constant current operation with automatic crossover and mode indication
● Analog programming
● LabView® and LabWindows® drivers
● CE, CSA, UL approvals
Specifications
| Switching Frequency | 7.5 V to 300 V models: nominal 125 kHz (250 kHz output ripple); 600 V model: nominal 62.5 kHz (125 kHz output ripple) | Time Delay | 4 sec maximum from power on until output stable | Voltage Mode Transient Response Time | 1 ms for output voltage to recover within 0.5% of its previous level after a step change in load current of up to 50% of rated output | Maximum Voltage Differential | ±600 Vdc from output to safety ground | Remote Start/Stop and Interlock | 2.5-15 V signal or TTL-compatible input, selectable logic | Remote Analog Programming | Voltage and current programming inputs (source must be isolated): 0-5 k, 0-10 k resistances; 0-5 V (default), 0-10 V voltage sources | Remote Analog Monitoring | Voltage and current monitor outputs 0-5 V (default), 0-10 V ranges for 0-100% of output | Remote Programming & Monitoring Accuracy | 1% zero to full scale output for the default range | Front Panel Voltage and Current Control | 10-turn voltage and current potentiometers | Front Panel Voltage Control Resolution | 0.02% of maximum voltage | Main Output Connector | 7.5 to 40 V models: nickel-plated copper bus bars; 60 to 600 V models: 4-terminal wire clamp connector for DC output and local sense | Protection Features | Over-voltage protection and Over-temperature protection | Approvals | CE-marked units meet: EN61010-1, EN61000-6-2 and EN61000-6-4; CSA C/US certified to UL61010-1B and CSA C22.2 No 1010.1; Meets USA EMC standard: FCC, part 15B, Class A; Meets Canadian EMC standard: ICES-001, Class A. |
|
|
| Operating Temperature | 0°C to 40°C | Storage Temperature | -40°C to 85°C | Humidity Range | Up to 80% RH, non-condensing |
|
|
| Dimensions | Width: 8.5” (216 mm) Height: 3.4” (86.4 mm) Depth: 18.6” (472.2 mm) | Weight | Approximately 14 lbs. ( 6.4 kg ) |
|
|
| Voltage Ranges | 85-250 VAC, 47-63 Hz, power factor corrected. Derate maximum output power to 900 W for AC input less than 95 V | Power Factor | 99 minimum for full load and 120 Vac input | Current | 13 A maximum at 100 Vac; 11 A maximum at 120 Vac; 6 A maximum at 220 Vac | AC Input Connector Type | IEC 320 connector |
|
|
| Model | Output Voltage | Output Current | Output Power | XHR 7.5-130 | 0-7.5 V | 0-130 C | 975 W | XHR 20-50 | 0-20 V | 0-50 C | 1000 W | XHR 33-33 | 0-33 V | 0-33 C | 1089 W | XHR 40-25 | 0-40 V | 0-25 C | 1000 W | XHR 60-18 | 0-60 V | 0-18 C | 1080 W | XHR 100-10 | 0-100 V | 0-10 C | 1000 W | XHR 150-7 | 0-150 V | 0-7 C | 1050 W | XHR 300-3.5 | 0-300 V | 0-3.5 C | 1050 W | XHR 600-1.7 | 0-600 V | 0-1.7 C | 1050 W |
|
|
Output : At the front panel posts |
| Model | Output Ratings | Voltage (VDC) | Current (ADC) | XHR 7.5-130 | 0-7.5 | 0-130 | XHR 20-50 | 0-20 | 0-50 | XHR 33-33 | 0-33 | 0-33 | XHR 40-25 | 0-40 | 0-25 | XHR 60-18 | 0-60 | 0-18 | XHR 100-10 | 0-100 | 0-10 | XHR 150-7 | 0-150 | 0-7 | XHR 300-3.5 | 0-300 | 0-3.5 | XHR 600-1.7 | 0-600 | 0-1.7 |
|
|
| Model | Line Regulation (2) | Load Regulation (3) | Voltage | Current | Voltage | Current | XHR 7.5-130 | 3 mV | 14 mA | 3 mV | 66 mA | XHR 20-50 | 4 mV | 6 mA | 4 mV | 26 mA | XHR 33-33 | 5 mV | 4.3 mA | 5 mV | 18 mA | XHR 40-25 | 8 mV | 3.5 mA | 6 mV | 14 mA | XHR 60-18 | 8 mV | 2.8 mA | 8 mV | 10 mA | XHR 100-10 | 12 mV | 2 mA | 12 mV | 6 mA | XHR 150-7 | 17 mV | 1.7 mA | 17 mV | 4.5 mA | XHR 300-3.5 | 32 mV | 1.3 mA | 32 mV | 3 mA | XHR 600-1.7 | 62 mV | 1.2 mA | 62 mV | 2 mA |
|
|
| Model | Meter Accuracy | Output Noise (0-20 MHz) Voltage (p-p) | Output Ripple (rms) Voltage | Voltage (0.5% to 1% of Vmax + 1 count) | Current (0.5% of Imax + 1 count) | XHR 7.5-130 | 0.09 V | 1.4 A | 70 mV | 10 mV | XHR 20-50 | 0.3 V | 0.6 A | 70 mV | 10 mV | XHR 33-33 | 0.43 V | 0.43 A | 75 mV | 7.5 mV | XHR 40-25 | 0.5 V | 0.35 A | 75 mV | 7.5 mV | XHR 60-18 | 0.7 V | 0.19 A | 75 mV | 10 mV | XHR 100-10 | 1.1 V | 0.11 A | 100 mV | 10 mV | XHR 150-7 | 1.6 V | 0.08 A | 150 mV | 20 mV | XHR 300-3.5 | 4 V | 0.05 A | 250 mV | 30 mV | XHR 600-1.7 | 7 V | 0.03 A | 500 mV | 120 mV |
|
|
| Model | Load Regulation (3) | Meter Accuracy | Voltage | Current | Voltage (0.5% to 1% of Vmax + 1 count) | Current (0.5% of Imax + 1 count) | XHR 7.5-130 | 3 mV | 66 mA | 0.09 V | 1.4 A | XHR 20-50 | 4 mV | 26 mA | 0.3 V | 0.6 A | XHR 33-33 | 5 mV | 18 mA | 0.43 V | 0.43 A | XHR 40-25 | 6 mV | 14 mA | 0.5 V | 0.35 A | XHR 60-18 | 8 mV | 10 mA | 0.7 V | 0.19 A | XHR 100-10 | 12 mV | 6 mA | 1.1 V | 0.11 A | XHR 150-7 | 17 mV | 4.5 mA | 1.6 V | 0.08 A | XHR 300-3.5 | 32 mV | 3 mA | 4 V | 0.05 A | XHR 600-1.7 | 62 mV | 2 mA | 7 V | 0.03 A |
|
|
| Model | Output Noise (0-20 MHz) Voltage (p-p) | Output Ripple (rms) Voltage | Drift (8 hours) (4) | Voltage (0.05% of Vmax) | Current (0.1% of Imax) | XHR 7.5-130 | 70 mV | 10 mV | 3.75 mV | 130 mA | XHR 20-50 | 70 mV | 10 mV | 10 mV | 50 mA | XHR 33-33 | 75 mV | 7.5 mV | 16.5 mV | 33 mA | XHR 40-25 | 75 mV | 7.5 mV | 20 mV | 25 mA | XHR 60-18 | 75 mV | 10 mV | 20 mV | 18 mA | XHR 100-10 | 100 mV | 10 mV | 50 mV | 10 mA | XHR 150-7 | 150 mV | 20 mV | 75 mV | 7 mA | XHR 300-3.5 | 250 mV | 30 mV | 150 mV | 3.5 mA | XHR 600-1.7 | 500 mV | 120 mV | 300 mV | 1.7 mA |
|
|
| Model | Temperature Coefficient (5) | Maximum Remote Sense Line Drop Compensation 6 | OVP Adjustment Range (5%to 110% of Vmax) | Efficiency (7) | Voltage (0.02% of Vmax/°C) | Current (0.03% of Imax/°C) | XHR 7.5-130 | 1.5 mV | 39 mA | 3 V / line | 0.375-8.25 V | 81% | XHR 20-50 | 4 mV | 15 mA | 5 V / line | 1-22 V | 83% | XHR 33-33 | 6.6 mV | 9.9 mA | 5 V / line | 1.65-36.3 V | 83% | XHR 40-25 | 8 mV | 7.5 mA | 5 V / line | 2-44 V | 83% | XHR 60-18 | 12 mV | 5.4 mA | 5 V / line | 3-66 V | 84% | XHR 100-10 | 20 mV | 3 mA | 5 V / line | 5-110 V | 84% | XHR 150-7 | 30 mV | 2.1 mA | 5 V / line | 7.5-165 V | 85% | XHR 300-3.5 | 60 mV | 1.1 mA | 5 V / line | 15-330 V | 85% | XHR 600-1.7 | 120 mV | 0.48 mA | 5 V / line | 30-660 V | 85% | Specifications subject to change without notice. 1. Specifications indicate typical performance at 25°C ± 5°C, nominal line input of 120 Vac. 3. For 0-100% load variation, with constant nominal line voltage. Measured at the rear panel output connector unless stated otherwise. 4. Maximum drift over 8 hours with constant line, load, and temperature, after 30-minute warm-up. 5. Change in output per °C change in ambient temperature, with constant line and load. 6. Line drop is subtracted from total voltage available at supply output. 7. Typical efficiency at 115 Vac input and rated output power. 8. Apply accuracy specifications according to the following voltage program accuracy example: Set a model 20-50 power supply to 10 V. The expected result will be within the range of 10 V ± 75 mV ± 0.12% of the set voltage of 10 V. |
|
|
產品型錄下載