產品名稱:(1500W) 1U DC power supply產品型號:Sorensen XG 1500 WattSorensen XG 1500 Watt1500 Watt, 1U DC power supply with constant voltage and constant current modesKey ModesOutput Auto Start Mode (Auto Restart)The Auto Start mode establishes the state of the output of the power supply after recove

產品介紹

產品名稱:(1500W) 1U DC power supply

產品型號:Sorensen XG 1500 WattSorensen XG 1500 Watt
1500 Watt, 1U DC power supply with constant voltage and constant current modes

Key Modes
Output Auto Start Mode (Auto Restart)
The Auto Start mode establishes the state of the output of the power supply after recovery from a complete power cycle (all front panel LEDs are not illuminated), or after recovery from a PC failure or reboot. If Auto Start mode is set to On, the power supply output will return to its previous value. Also, after the loss of any remote digital control, the XG unit will remain active in its last programmed setting and will not disrupt any test process.

Auxiliary Auto Start Mode 
The Auxiliary Auto Start mode determines the state of the auxiliary output after a complete power cycle (all front panel LEDS are not illuminated). With Auxiliary Auto Start mode turned to On, the auxiliary output will be activated after the power supply is powered up again.

Foldback Mode
Foldback mode is used to disable the output when a transition is made between the operating modes. The power supply will turn off/disable the output and lock in foldback mode after a specified delay if the power supply transitions into CV mode or into CC mode, depending on the foldback mode settings. This feature is particularly useful for protecting current or voltage sensitive loads. Foldback can be set to trigger a switch when transitioning from CV to CC mode or from CC to CV mode.

Specifications

Output Ratings
ModelOutput Voltage¹Output Current²Output Power³
XG 6-2206 V220 A1320 W
XG 8-187.58 V187.5 A1500 W
XG 12.5-12012.5 V120 A1500 W
XG 20-7620 V76 A1520 W
XG 30-5030 V50 A1500 W
XG 40-3840 V38 A1520 W
XG 60-2560 V25 A1500 W
XG 80-1980 V19 A1520 W
XG 100-15100 V15 A1500 W
XG 150-10150 V10 A1500 W
XG 300-5300 V5 A1500 W
XG 600-2.6600 V2.6 A1560 W
Line Regulation
ModelVoltage (0.005% of rated 
output voltage +2 mV)4
Current (0.01% of rated 
output current +2 mA)5

XG 6-2202.3 mV24 mA
XG 8-187.52.4 mV20.7 mA
XG 12.5-1202.62 mV14 mA
XG 20-763.0 mV9.6 mA
XG 30-503.5 mV7 mA
XG 40-384 mV5.8 mA
XG 60-255 mV4.5 mA
XG 80-196 mV3.9 mA
XG 100-157 mV3.5 mA
XG 150-109.5 mV3 mA
XG 300-517 mV2.5 mA
XG 600-2.632 mV2.26 mA
Load Regulation
ModelVoltage (0.005% of rated 
output voltage + 2 mV)6
Current (0.02% of rated 
output current +5 mA)7

XG 6-2202.3 mV49 mA
XG 8-187.52.4 mV42.5 mA
XG 12.5-1202.62 mV29 mA
XG 20-763.0 mV20.2 mA
XG 30-503.5 mV15 mA
XG 40-384 mV12.6 mA
XG 60-255 mV10 mA
XG 80-196 mV8.8 mA
XG 100-157 mV8 mA
XG 150-109.5 mV7 mA
XG 300-517 mV6 mA
XG 600-2.632 mV5.5 mA
Output Ratings
ModelOutput Noise (rms, 300 kHz)Output Ripple 
(p-p, 20 MHz)
VoltageCurrent8Voltage
XG 6-2208 mV400 mA50 mV
XG 8-187.58 mV319 mA50 mV
XG 12.5-1208 mV206 mA50 mV
XG 20-768 mV136 mA50 mV
XG 30-508 mV120 mA50 mV
XG 40-388 mV81 mA50 mV
XG 60-258 mV63 mA50 mV
XG 80-198 mV45 mA80 mV
XG 100-158 mV35 mA80 mV
XG 150-1010 mV29 mA100 mV
XG 300-525 mV18 mA150 mV
XG 600-2.650 mV11 mA250 mV
1. Maximum output voltage is guaranteed to be ≤ 0.2% of the rated voltage at zero output setting, using the front panel or digital remote programming modes.
2. Maximum output current is guaranteed to be ≤ 0.4% of the rated current at zero output setting, using the front panel or digital remote programming modes, and when measured with rated load resistance.
3. Total output power is also based on AUX1 Output Voltage (5 V) and AUX1 Output Current (0.5 A) and AUX2 Output Voltage (15 V) and AUX2 Output Current (0.5 A).
4. From 85–132 Vac or 170–265 Vac, constant load.
5. From 85–132 Vac or 170–265 Vac, constant load.
6. From no load to full load, constant input voltage.
7. For load voltage change, equal to the unit voltage rating, constant input voltage.
8. For 6 V models the current ripple is measured at 2–6 V output voltage and full output current. For all other models, the current ripple is measured at 10–100% output voltage and full output current.
Output Ratings
ModelMaximum Recommended Remote Sense Line Drop Compensation per Line 9Up-prog. Response Time, 0~Vmax 10Efficiency (100/200 VAC input) 11
XG 6-2201 V60 ms75/77%
XG 8-187.51 V60 ms77/79%
XG 12.5-1201 V60 ms81/84%
XG 20-761.5 V60 ms82/85%
XG 30-502 V60 ms83/86%
XG 40-382 V60 ms84/88%
XG 60-253 V60 ms84/88%
XG 80-195 V100 ms84/88%
XG 100-155 V100 ms84/88%
XG 150-105 V100 ms84/88%
XG 300-55 V150 ms84/88%
XG 600-2.65 V250 ms84/88%
Output Ratings
ModelDown-prog. Response Time: Full LoadDown-prog. Response Time: No LoadOver-Voltage Trip Point
XG 6-22050 ms300 ms0.5-7.5 V
XG 8-187.550 ms400 ms0.5-10 V
XG 12.5-12050 ms500 ms1-15 V
XG 20-7650 ms600 ms1-24 V
XG 30-5050 ms700 ms2-36 V
XG 40-3850 ms800 ms2-44 V
XG 60-2550 ms900 ms5-66 V
XG 80-1980 ms1000 ms5-88 V
XG 100-15100 ms1200 ms5-110 V
XG 150-10150 ms1800 ms5-165 V
XG 300-5150 ms2200 ms5-330 V
XG 600-2.6250 ms3500 ms5-660 V
9. When using remote sense, the total of the load voltage and the load line drops must not exceed the rated output of the power supply. For example, for an XG 6-220 in an application with 1 V of load line loss (0.5 V/Line), the maximum available load voltage would be 6-1=5 V. Note: The unit may operate at higher output voltages than this, but there is no guarantee That the power supply will meet performance specifications. Ultimately, the upper limit of the output voltage will be determined by internal circuitry of the power supply (non-adjustable) 
10. With rated, resistive load. 
11. At 100/200 Vac input voltage and maximum output power. Applies to all footnotes: Programming and Readback: RS-232, RS-485, USB built in. GP1B, Ethernet optional. Specifications are guaranteed from 1% to 100% of the rated output voltage, current, and power. 
* Typical 

Note: All specifications are subject to change.
AC Line Input Specifications
Rated AC Input Voltage/Frequency100–240 Vac, 47–63 Hz
Operational AC Input Voltage/Frequency85–265 Vac continuous, 47–63 Hz, single phase
Input Current (at 100/200 Vac)23/12 A
Inrush Current (100/200 Vac)Less than: 50 A
Power Factor Correction0.99@100/200 Vac, rated output power
Programming Mode

APGISOLDIGITAL
Voltage & Current Output
Voltage Programming
0-100% 2~up to 10 V, programmable

Voltage & Current Output
Resistive Programming
0-100% 2~up to 10 kΩ, programmable

Voltage Output Resistor Programming0-100% 2~up to 10 kΩ, programmable

Output Voltage and Current Monitor0-100% 2~up to 10 V, programmable

Voltage Programming Accuracy (mV)1± 0.5% of rated output voltage, max (0-4V/4K range)
± 0.1% of rated output voltage
Current Programming Accuracy (mV)1± 1% of rated output current,
max (0-4V/4K range)

± 0.2% of rated output current
Voltage Readback Accuracy (mV)± 1% of rated output voltage
± 0.1% of rated output voltage
Current Readback Accuracy (mV)± 1% of rated output current
± 0.2% of rated output current
Isolation (Prog and Readback Lines)With respect to chassis potential: 500 VWith respect to:
chassis potential: 600 V
negative or positive main output 1500 V
negative or positive auxiliary output 300 V

Voltage and Current
Programming Resolution


0.012% of full scale
Voltage and Current
Readback Resolution



Parallel OperationUp to 4 units in master / slaveUp to 4 units in master / slaveUp to 4 units in master / slave
Series Operation
Up to 2 units (with external diodes)Up to 2 units (with external diodes)
Constant Voltage (CV) Constant
Current (CC) Indicator
CV: TTL High (4-5 V)
CC TTL Low (0-0.6 V)


Shutdown Control 2
Logic low 0.0 - 1.4 V
Logic high 2.0 - 15 V
Dry contact compatible

AUX On/Off Control
TTL level or dry contact compatible
Power Supply Status Signal
TTL high: OK (4-5 V)
TTL low: fail (0-0.6 V)

Interlock Enable/Disable
Dry contact. Open/Short: On or
Off programmable

1. Typical APG or isolated APG accuracy can be improved to max accuracy by user calibration at the specific range selected 
2. The shutdown input has user selectable negative logic operation via front panel or remote digital input/output 

Note: All specifications are subject to change.
Output Performance Specifications
Temperature Coefficient100 PPM/° C from rated output voltage, after a 30-minute warm-up*
Drift (8 hours)0.05% of rated output voltage & current over an 8 hour interval with constant line, load & temperature, after a 30-minute warm-up
Hold-up TimeTypical 20 ms at any rated input line.
Transient Response Time13Less than 1 ms for 6 V to 60 V models. Less than 2 ms for 80 V to 600 V models*
Meter Accuracy0.5% ± 1 count
Aux output 3+5 V: +0.4 V, – 0.5 V at 0.4 A
+15 V: +1.2 V, – 1.4 V at 0.4 A
Isolation 121500Vac or 2121Vdc between mains terminals and accessible conductive parts / chassis ground. 
Output to chassis 500Vac.
Environmental Specifications (Indoor use)
Operating Temperature Range32°F to 122°F, 100% load (0°C to 50°C)
Storage Temperature Range-4°F to 158°F (–20° C to 70°C)
Operating Humidity Range30–90% RH (no condensation)
Storage Humidity Range10–95% RH (no condensation)
Operating AltitudeUp to 6,500 feet (2,000 m)
Installation CategoryII (IEC 1010-1)
Pollution Degree2 (IEC 1010-1)
Mechanical Specifications
XG 1700 Watt (W×H×D)16.8 x 1.7 x 19.0 inch (429 x 43.6 x 483 mm without rack mount ears)
Weight22 lb (10 kg)
CoolingForced air cooling by internal fans
Regulatory Approvals
Safety
 
CSA 22.2 No. 61010-1, 60950-1-07 and UL61010-1, UL60950-1-(2nd Ed) 12. Marked with cCSAus, CE for EMC & low voltage directive
EMCComplies with EN61326-1 
Complies with EN55022, Class B, FCC Part 15B for conducted emissions 
Complies with EN55022, Class A, FCC Part 15A for radiated emissions 
Complies with EN61000-4 series of standards for immunity

* Typical
1. Time for the output voltage to recover within 0.05% at its rated output for a load change 10-90% of rated ouput current. Output set point 10-100%
2. Double insulation on primary to secondary isolation barriers. Basic insulation primary to protective earth ground.
3. Current: 0.51 A minimum guaranteed, 0.72 A typically available. Overcurrent protection (each output) is automatic, non-latching. When OCP is tripped the aux voltage folds back and will recover to nominal condition
when the over current condition is removed (typ. <0.2A). To protect external circuits attached to the aux outputs it is recommended that customers use an appropriately rated fuse in series with the aux outputs set point 10-100%

Note: All specifications are subject to change.